What makes up TIA Portal?
Totally Integrated Automation (TIA) Portal is an all-in-one engineering platform that allows users to effectively commission, program, and diagnose Siemens automation hardware and software, all within a single software interface that allows for integrated system diagnostics, communication, and other features. As additional versions are released, newly released hardware and updated programming functions are added to the wide variety of products and options TIA Portal offers.
TIA Portal encompasses several software packages to program various Siemens automation and drive components. For all software packages listed, various support services (software upgrade services [SUS], license upgrades, add-on features, etc.) are available. As of TIA Portal V14 SP1, all TIA Portal software packages are also compatible on a Windows 10 64-bit operating system. For specific inquiries about an application, please don’t hesitate to contact AWC for any technical questions or further assistance!
STEP 7 – SIMATIC S7 PLC Programming Software
What PLC hardware do you have? | What PLC software edition do you need?* |
---|---|
S7-1200 | STEP 7 Basic** |
S7-1500 and S7-1500 Software Controller | STEP 7 Professional |
S7-300 (FW >= V2.6) | STEP 7 Professional *** |
S7-400 (excluding S7-400H CPUs) | STEP 7 Professional *** |
ET200SP CPU | STEP 7 Professional |
The Programming Style Guide and Programming Guideline for SIMATIC S7-1200/S7-1500 provide tips, tricks, and recommended best practices for developing a project in TIA Portal.
* Both S7-PLCSIM (for simulating PLCs) and WinCC Basic (for configuring SIMATIC Basic Panels) are included with both STEP 7 Professional and STEP 7 Basic at no additional cost.
** If any other SIMATIC S7 platforms in addition to the S7-1200 will be programmed, STEP 7 Professional will be required.
***For S7-300s with FW < V2.6 or S7-7400H CPUs, STEP 7 V5.6 or STEP 7 Professional 2017 will be required.
STEP 7 Safety Programming Software – add-on package for programming fail-safe SIMATIC S7 PLCs
What PLC hardware do you have? | What PLC software edition do you need?* |
S7-1200FC | STEP 7 Safety Basic** |
S7-1500F and S7-1500F Software Controller, ET200SF-CPU | STEP 7 Safety Advanced |
S7-300F (FW >= 2.6) | STEP 7 Safety Advanced |
S7-400F | STEP 7 Safety Advanced |
ET200SP F-CPU | STEP 7 Safety Advanced |
The Programming Guideline for Safety with SIMATIC S7-1200/S7-1500 provide tips, tricks, and recommended best practices for developing a project in TIA Portal.
* The previous installation of the corresponding edition of STEP 7 is a pre-requisite for installing the STEP 7 Safety add-on.
** If any other SIMATIC S7 fail-safe CPUs in addition to the S7-1200FC will be programmed, STEP 7 Safety Advanced will be required.
WinCC – SIMATIC HMI Engineering Software
What HMI hardware do you have? | What HMI software edition do you need? |
HMI Basic Panels | WinCC Basic |
HMI Comfort Panels | WinCC Comfort |
PC single stations such as SIMATIC IPC | WinCC Advanced for engineering, WinCC Runtime Advanced for runtime** |
Multiple PC stations, SCADA | WinCC Professional for engineering*, WinCC Runtime Professional for runtime** |
HMI Unified Comfort Panels | WinCC Unified* |
*WinCC Professional and WinCC Unified cannot be installed in parallel with each other.
**WinCC Runtime Advanced and Professional are tag-based licenses that are loaded to the PC itself.
Startdrive – SINAMICS Drive Commissioning Software
What drive hardware do you have? | What functions are you trying to accomplish? | What drive software do you need? |
G120, S120, S210 | Commissioning and diagnostics | Startdrive Basic V16 |
G120, S120, S210 | Integrated Safety Acceptance Tests | Startdrive Advanced V16 |
G130, G150, S150 | Commissioning and diagnostics | Startdrive Basic V16 |
For tips and tricks on how to use the Startdrive features in a TIA Portal project, please review the Getting Started – SINAMICS Startdrive guide.
Additional platforms
The below software packages are used to configure and program hardware that is not available within TIA Portal; therefore in contrary to the above, these software packages are not integrated into TIA Portal.
What hardware do you have? | What software do you need? |
S7-300 (pre-2009), S7-400, S7-400H | STEP 7 V5.6 or STEP 7 Professional 2017 |
S7-200 | S7-Microwin |
LOGO! logic modules | LOGO! Soft Comfort |
Legacy SIMATIC HMI panels (Micro, TP, OP, MP) | WinCC flexible 2008 SP5 |
For information on how to transition from the S7-200 to the S7-1200, please review the Making the Transition from S7-200 to S7-1200 guide.